Comparison of the Reliability of “0.5” and “APEX” Mark Measurements in Two Frequency-based Electronic Apex Locators

Published:October 04, 2010DOI:https://doi.org/10.1016/j.joen.2010.08.048

      Abstract

      Introduction

      A measuring instrument must be both accurate and reliable. This study compared the reliability of the “0.5” and “APEX” mark measurements by using 2 impedance quotient-based electronic apex locators (EALs).

      Methods

      One hundred four extracted human premolars were used in this study. After access preparation, the teeth were embedded in an alginate model. By using 2 EALs (Root ZX and i-Root), the tooth length was measured at the “0.5” and “APEX” marks with K-files. The file was then cemented, and the apical 3–4 mm was trimmed for the photograph under an operating microscope. The distance between the tip of the file and major foramen (MF) was measured. The intraclass correlation coefficient, the Bland-Altman plot, and box plot were used to compare the reliability.

      Results

      The intraclass correlation coefficient ranged from 0.976–0.994, indicating excellent agreement in both “0.5” and “APEX” marks. The Bland-Altman plots showed that the limits of agreement (mean ± 2 standard deviations) were small enough to confirm that both marks of the 2 EALs can be used for clinical purposes. The distribution of the measurements and outliers was analyzed by using box plots, and it was found that there was no significant difference between the 2 marks.

      Conclusions

      There was no significant difference in the reliability of the “0.5” and “APEX” marks for locating the MF in both devices. Accordingly, knowing where each mark indicates is more important for determining the working length than which mark to choose.

      Key Words

      To read this article in full you will need to make a payment

      Purchase one-time access:

      Academic & Personal: 24 hour online accessCorporate R&D Professionals: 24 hour online access
      One-time access price info
      • For academic or personal research use, select 'Academic and Personal'
      • For corporate R&D use, select 'Corporate R&D Professionals'

      Subscribe:

      Subscribe to Journal of Endodontics
      Already a print subscriber? Claim online access
      Already an online subscriber? Sign in
      Institutional Access: Sign in to ScienceDirect

      References

        • ElAyouti A.
        • Weiger R.
        • Lost C.
        The ability of root ZX apex locator to reduce the frequency of overestimated radiographic working length.
        J Endod. 2002; 28: 116-119
        • Pratten D.H.
        • McDonald N.J.
        Comparison of radiographic and electronic working lengths.
        J Endod. 1996; 22: 173-176
        • Kim E.
        • Lee S.J.
        Electronic apex locator.
        Dent Clin North Am. 2004; 48: 35-54
        • Nekoofar M.H.
        • Ghandi M.M.
        • Hayes S.J.
        • Dummer P.M.
        The fundamental operating principles of electronic root canal length measurement devices.
        Int Endod J. 2006; 39: 595-609
      1. J. Morita Corp. Root ZX operation instructions. Kyoto, Japan, 2004:10.

        • Shabahang S.
        • Goon W.W.
        • Gluskin A.H.
        An in vivo evaluation of Root ZX electronic apex locator.
        J Endod. 1996; 22: 616-618
        • Tselnik M.
        • Baumgartner J.C.
        • Marshall J.G.
        An evaluation of root ZX and elements diagnostic apex locators.
        J Endod. 2005; 31: 507-509
        • Baldi J.V.
        • Victorino F.R.
        • Bernardes R.A.
        • et al.
        Influence of embedding media on the assessment of electronic apex locators.
        J Endod. 2007; 33: 476-479
        • Siu C.
        • Marshall J.G.
        • Baumgartner J.C.
        An in vivo comparison of the Root ZX II, the Apex NRG XFR, and Mini Apex Locator by using rotary nickel-titanium files.
        J Endod. 2009; 35: 962-965
        • Pascon E.A.
        • Marrelli M.
        • Congi O.
        • Ciancio R.
        • Miceli F.
        • Versiani M.A.
        An in vivo comparison of working length determination of two frequency-based electronic apex locators.
        Int Endod J. 2009; 42: 1026-1031
        • Ricucci D.
        • Langeland K.
        Apical limit of root canal instrumentation and obturation, part 2: a histological study.
        Int Endod J. 1998; 31: 394-409
        • Dummer P.M.
        • McGinn J.H.
        • Rees D.G.
        The position and topography of the apical canal constriction and apical foramen.
        Int Endod J. 1984; 17: 192-198
        • Lee S.J.
        • Nam K.C.
        • Kim Y.J.
        • Kim D.W.
        Clinical accuracy of a new apex locator with an automatic compensation circuit.
        J Endod. 2002; 28: 706-709
        • Mayeda D.L.
        • Simon J.H.
        • Aimar D.F.
        • Finley K.
        In vivo measurement accuracy in vital and necrotic canals with the Endex apex locator.
        J Endod. 1993; 19: 545-548
        • Dunlap C.A.
        • Remeikis N.A.
        • BeGole E.A.
        • Rauschenberger C.R.
        An in vivo evaluation of an electronic apex locator that uses the ratio method in vital and necrotic canals.
        J Endod. 1998; 24: 48-50
        • Wrbas K.T.
        • Ziegler A.A.
        • Altenburger M.J.
        • Schirrmeister J.F.
        In vivo comparison of working length determination with two electronic apex locators.
        Int Endod J. 2007; 40: 133-138
        • Hor D.
        • Krusy S.
        • Attin T.
        Ex vivo comparison of two electronic apex locators with different scales and frequencies.
        Int Endod J. 2005; 38: 855-859
        • Gulabivala K.
        • Stock C.
        Root canal system preparation.
        in: Gulabivala K. Stock C. Walker R.T. Endodontics. 3rd ed. Elsevier, Mosby, Edinburgh; New York2004: 142-144
        • Kaufman A.Y.
        • Keila S.
        • Yoshpe M.
        Accuracy of a new apex locator: an in vitro study.
        Int Endod J. 2002; 35: 186-192
      2. R Development Core Team. R: a language and environment for statistical computing.
        R Foundation for Statistical Computing, Vienna, Austria2009
        • Bland J.M.
        • Altman D.G.
        Statistical methods for assessing agreement between two methods of clinical measurement.
        Lancet. 1986; 1: 307-310
        • Fleiss J.L.
        The design and analysis of clinical experiments.
        John Wiley & Sons, New York1985 (8)
        • Kuttler Y.
        Microscopic investigation of root apexes.
        J Am Dent Assoc. 1955; 50: 544-552
        • Seo S.-H.
        • An H.
        • Lee S.-J.
        • Lim W.H.
        • Kim B.-R.
        Mixed dentition analysis using a multivariate approach.
        Korean J Orthod. 2009; 39: 112-119